Optimizing Heat Pump Control in an NZEB via Model Predictive Control and Building Simulation

EU regulations get stricter from 2028 on by imposing net-zero energy building (NZEB) standards on new residential buildings including on-site renewable energy integration. Heat pumps (HP) using thermal building mass, and Model Predictive Control (MPC) provide a viable solution to this problem. Howev...

Full description

Saved in:
Bibliographic Details
Main Authors: Christian Baumann, Philipp Wohlgenannt, Wolfgang Streicher, Peter Kepplinger
Format: Article
Language:English
Published: MDPI AG 2024-12-01
Series:Energies
Subjects:
Online Access:https://www.mdpi.com/1996-1073/18/1/100
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:EU regulations get stricter from 2028 on by imposing net-zero energy building (NZEB) standards on new residential buildings including on-site renewable energy integration. Heat pumps (HP) using thermal building mass, and Model Predictive Control (MPC) provide a viable solution to this problem. However, the MPC potential in NZEBs considering the impact on indoor comfort have not yet been investigated comprehensively. Therefore, we present a co-simulative approach combining MPC optimization and <i>IDA ICE</i> building simulation. The demand response (DR) potential of a ground-source HP and the long-term indoor comfort in an NZEB located in Vorarlberg, Austria over a one year period are investigated. Optimization is performed using Mixed-Integer Linear Programming (MILP) based on a simplified RC model. The HP in the building simulation is controlled by power signals obtained from the optimization. The investigation shows reductions in electricity costs of up to 49% for the HP and up to 5% for the building, as well as increases in PV self-consumption and the self-sufficiency ratio by up to 4% pt., respectively, in two distinct optimization scenarios. Consequently, the grid consumption decreased by up to 5%. Moreover, compared to the reference PI controller, the MPC scenarios enhanced indoor comfort by reducing room temperature fluctuations and lowering the average percentage of people dissatisfied by 1% pt., resulting in more stable indoor conditions. Especially precooling strategies mitigated overheating risks in summer and ensured indoor comfort according to EN 16798-1 class II standards.
ISSN:1996-1073