Fault-tolerant Shunt Active Power Filter Based on Component Redundancy and Its Control Strategy
Shunt active power filter (SAPF) is based on the three-phase six-switch topology. In order to improve its flexibility whenapplied in industrial field, it proposed a three-phase four-switch fault-tolerant SAPF based on component redundancy. The structure and operation mode of the fault-tolerant circu...
Saved in:
| Main Authors: | , , , |
|---|---|
| Format: | Article |
| Language: | zho |
| Published: |
Editorial Office of Control and Information Technology
2015-01-01
|
| Series: | Kongzhi Yu Xinxi Jishu |
| Subjects: | |
| Online Access: | http://ctet.csrzic.com/thesisDetails#10.13889/j.issn.2095-3631.2015.04.003 |
| Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
| Summary: | Shunt active power filter (SAPF) is based on the three-phase six-switch topology. In order to improve its flexibility whenapplied in industrial field, it proposed a three-phase four-switch fault-tolerant SAPF based on component redundancy. The structure and operation mode of the fault-tolerant circuit were analyzed in details. Considering about the voltage fluctuation and unbalance of DC side capacitor when one-phase fault occurred, voltage stabilization control and equalization control were designed. Due to the circuit of threephase six-switch four-wire would be converted into three-phase four-switch three-wire system, corresponding control strategy in the fault-tolerant status was studied to guarantee the output symmetry among three-phase. Experimental results of a 50 kVA prototype have validated the efficiency and feasibility of the proposed control strategy. |
|---|---|