Analysis of Flexible Output Power Adjustment for Traction Substation inElectrified Railway

The catenary of electrified railway adopts single-phase single-side power supply mode, the power supply capacity of transformer winding supplying power to each power supply section is fixed, and it is difficult to support each other between power supply sections. This paper proposed a method to adju...

Full description

Saved in:
Bibliographic Details
Main Authors: HAO Zuolin, XU Gencai, WU Liran, HU Liang
Format: Article
Language:zho
Published: Editorial Office of Control and Information Technology 2020-01-01
Series:Kongzhi Yu Xinxi Jishu
Subjects:
Online Access:http://ctet.csrzic.com/thesisDetails#10.13889/j.issn.2096-5427.2020.06.009
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The catenary of electrified railway adopts single-phase single-side power supply mode, the power supply capacity of transformer winding supplying power to each power supply section is fixed, and it is difficult to support each other between power supply sections. This paper proposed a method to adjust output power of traction substation by balanced power supply technology. It connects adjacent power supply sections by high-power AC-DC-AC converter and reduces 20% to 40% of the peak value of impact load on each power supply arm. The proposed method realizes flexible output power adjustment in the traction substation, and ensures power supply capacity and security.